The EnergyCell RE valve regulated lead acid battery is designed for high power density and renewable energy cycling applications. This battery utilizes Absorbed Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance. The EnergyCell RE also features low profile terminals with threaded copper alloy inserts providing reduced maintenance and increased safety.

Technical Specifications

  ENERGYCELL 170RE ENERGYCELL 200RE
Cells Per Unit: 6 6
Voltage Per Unit: 12 Vdc 12 Vdc
Operating Temperature Range: Discharge: -40°F (-40°C) to +160°F (71°C) Charge: -10°F (-23°C) to +140°F (60°C)
Optimal Operating Temperature Range: +74°F (23°C) to +80°F (27°C)
Recommended Maximum Charging
Current Limit per String:
25 Adc 30 Adc
Float Voltage Charge: 13.62 to 13.8 Vdc/unit Average at 77°F (25°C)
Equalization and Cycle
Service Charging Limits:
14.4 to 14.8 Vdc/unit Average at 77°F (25°C)
Self Discharge: Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures.
Temperature Compensation Factor
(Charging):
5mV per degree C per cell (2V)
Terminal: Threaded copper alloy insert terminal to accept ¼-20 UNC bolt
Terminal Hardware Initial Torque: 110 in-lbs (12.4 Nm)
Weight (lbs/kg): 115 lbs (52 kg) 131 lbs (60 kg)
Dimensions: 11.14 x 22.01 x 4.95” (28.3 x 55.9 x 12.6 cm) 12.60 x 22.01 x 4.95” (32.0 x 55.09 x 12.6 cm)